Troubleshooting
Each entry gives a symptom, its usual causes and what to check. Work through the checks in order. The drive's own fault codes are not defined yet; see the last section.
Host interface
ip link set can0 up fails with "RTNETLINK answers: Invalid argument"
Causes: the bit rate is not set, or you set fd on or dbitrate on an adapter or driver without CAN FD support.
- Run
sudo dmesg | tail. The driver logs the reason, for examplebit-timing not yet defined. - Set the bit rate before you bring the interface up. See CAN FD on Linux.
- If the error appears only with
fd on, check that the adapter and its driver support CAN FD.
"RTNETLINK answers: Device or resource busy" when you change the bit rate
Cause: the interface is up. Run sudo ip link set can0 down, change the bit rate, then bring it up again.
cansend reports that the interface is not CAN FD capable
Cause: the interface MTU is 16, so it accepts only classic frames.
- Run
ip link show can0and check formtu 72. - On a real adapter, set
fd ontogether withdbitrate. - On a virtual interface, run
sudo ip link set vcan0 mtu 72.
"write: No buffer space available"
Cause: the transmit queue is full because frames are not leaving the controller. Usually no other node acknowledges them, or the controller is bus-off.
- Check that the drive is powered and connected.
- Check the controller state with
ip -details link show can0. - Work through No frames from the drive.
- If the error appears only during bursts, raise the queue length:
sudo ip link set can0 txqueuelen 1000.
CAN bus
No frames from the drive
- Check the supply: 48 V at the drive, and the supply is not in current limit.
- Start
candump -td can0before you switch the drive on. If the heartbeat is off (0x1017 = 0), the drive sends only its boot-up frame, once, at power-on. - Check that the host bit rates match the drive's (factory values TBD).
- Measure CAN_H to CAN_L with everything unpowered: about 60 Ω. See Electrical and CAN wiring.
- Check that CAN_H and CAN_L are not swapped and that CAN ground is connected.
- If an update was interrupted, the drive may be waiting in its bootloader. How it shows itself on the bus is TBD. See Firmware updates.
The interface goes to ERROR-PASSIVE when you send
Cause: no node acknowledges the frames.
- Check that the drive is powered.
- Check that the bit rates match on both sides.
- Check the wiring and termination.
The interface goes to BUS-OFF
Causes: a bit-rate or sample-point mismatch, missing or extra termination, swapped CAN_H and CAN_L, or a classic CAN node that is not CAN FD tolerant on a bus that carries CAN FD frames.
- Fix the cause. The checks above apply.
- Restart the interface:
sudo ip link set can0 down, thensudo ip link set can0 up. Withrestart-msset, the controller restarts by itself.
Error counters rise slowly or errors come and go
Causes: marginal bit timing, long stubs, missing ground, or termination at the wrong place.
Set the same sample points on all nodes.
Shorten stubs. Use twisted pair for CAN_H and CAN_L.
Turn on bus-error reporting and watch the error frames:
sudo ip link set can0 down sudo ip link set can0 type can bitrate 1000000 dbitrate 5000000 fd on berr-reporting on sudo ip link set can0 up candump -e can0,0:0,#FFFFFFFF
CANopen
An SDO request gets no response
python-canopen reports No SDO response received.
- Check the node ID: read it from the boot-up or heartbeat frame (
0x700 + <node-id>). - Check the NMT state in the heartbeat byte. In Stopped (0x04) the drive does not answer SDOs. Send Enter pre-operational:
cansend can0 000#80NN, whereNNis the node ID in hexadecimal.
An SDO request is aborted
The abort frame starts with 0x80. Bytes 4–7 hold the abort code (little-endian). These codes are defined in CiA 301:
| Abort code | Meaning | What to check |
|---|---|---|
| 0x05040000 | SDO protocol timed out | Bus load, drive state |
| 0x05040001 | Command specifier not valid or unknown | The first byte of the request |
| 0x06010000 | Unsupported access to an object | Access type of the object |
| 0x06010001 | Attempt to read a write-only object | Object access |
| 0x06010002 | Attempt to write a read-only object | Object access |
| 0x06020000 | Object does not exist | Index; the device description file |
| 0x06040041 | Object cannot be mapped to the PDO | PDO mapping |
| 0x06040042 | Mapped objects exceed the PDO length | PDO mapping |
| 0x06070010 | Data type or length does not match | Size of the value you write |
| 0x06090011 | Sub-index does not exist | Sub-index |
| 0x06090030 | Value range exceeded | Value |
| 0x06090031 | Value too high | Value |
| 0x06090032 | Value too low | Value |
| 0x08000020 | Data cannot be transferred or stored | Drive state |
| 0x08000021 | Not possible because of local control | Drive state |
| 0x08000022 | Not possible in the present device state | NMT state, CiA 402 state |
The drive does not reach Operation enabled
Read the statusword (0x6041) and find the state with the table in CANopen (CiA 402).
| State you read | Cause | What to do |
|---|---|---|
| Fault | A fault is active | Read 0x603F (error code) and 0x1001 (error register). Remove the cause. Write 0x0080, then 0x0006. |
| Switch on disabled, after Shutdown | Wrong controlword value, or the drive cannot switch on | Check that you wrote 0x0006. Check the supply voltage. Check the STO input (how STO shows in the statusword is TBD). |
| Ready to switch on or Switched on | Commands skipped or sent too fast | Send 0x0006, 0x0007, 0x000F in order. Wait for each state in the statusword. |
If 0x6061 does not show the mode you wrote to 0x6060, the drive does not support that mode. Read 0x6502.
PDOs do not arrive
- Check that the drive is in NMT operational (heartbeat byte 0x05). PDOs work only there.
- For transmission type 1, check that the host sends SYNC (0x080).
- Change PDO mapping only in pre-operational. In operational the drive can refuse it with abort 0x08000022.
- Read the PDO COB-ID (0x1800:01 or 0x1400:01). If bit 31 is set, the PDO is disabled.
The joint goes free during operation
Cause: the drive detected a fault and switched torque off, or the STO function was triggered.
- Read the statusword. Check bit 3 (Fault).
- Read 0x603F, the EMCY frames (
candump can0,080:780) and the UDS fault codes. - Check the STO wiring.
UDS
No response to UDS requests
- Check the request and response CAN IDs (TBD). Watch both with
candump. - Check whether the drive needs padded 8-byte frames (TBD).
- A non-default session ends after 5 s without requests. Send TesterPresent (
3E 80) or open the session again.
A UDS request gets a negative response
The response is 7F <service ID> <NRC>. Look up the NRC in UDS diagnostics. The most common:
| NRC | What to do |
|---|---|
| 0x7F, 0x7E | Change to the session the service needs. |
| 0x33 | Unlock with SecurityAccess (0x27). |
| 0x22 | The drive's state does not allow the request. Switch torque off and unload the joint. |
| 0x31 | Check the DID or routine ID. |
Short responses arrive but long ones time out
Cause: ISO-TP flow control does not reach the drive, or the frame length does not match.
- Check that the host sends flow control on the request CAN ID.
- Check that
tx_data_lengthandcan_fdin the ISO-TP parameters match the bus. - Check padding (TBD).
Mechanical
The output does not turn freely by hand, unpowered
- Remove anything that touches the output face: frame, cables, fixture.
- Check the screws in the output M4 holes. Each must be shorter than the clamped thickness plus 3.5 mm.
- Check that nothing is screwed into the 3 × M5 fixture holes.
- If the output still binds with nothing attached, do not power the drive and do not open it.
Firmware updates
The updater refuses to flash a drive
Cause: the joint holds load or torque is on. Unload the joint, switch torque off (Switch on disabled) and run the update again. The response the drive sends in this case is TBD.
The drive reports the old firmware version after an update
Causes: the signature check failed and the drive did not install the image, or the new image failed its self-test and the drive went back to the previous image.
- Read the fault codes over UDS.
- Check the image file, then run the update again.
The drive does not start after an interrupted update
The drive is waiting in its bootloader. Run the update again. You do not need to power-cycle or open the drive.
Drive fault codes
The drive's EMCY error codes and UDS DTCs are not defined yet.
| Code | Meaning | What to do |
|---|---|---|
| TBD | TBD | TBD |