CANopen (CiA 402)
The drive is a CANopen device with the CiA 402 drive profile. This page covers the CAN IDs, network management, reading and writing objects, the CiA 402 state machine, modes of operation, the standard objects, cyclic control with PDOs and SYNC, and emergency messages. The content follows CiA 301 and CiA 402. Drive-specific values are TBD.
Status
| Item | Value |
|---|---|
| Device description file | Not released. Format (EDS, CiA 306, or XDD, CiA 311): TBD. |
| Factory node ID | TBD |
| Supported modes of operation | TBD. Read 0x6502 on the drive. |
| Implemented objects | TBD. The device description file will list them. |
| Default PDO mapping | TBD |
| Position and velocity units | TBD |
| Rated torque (0x6076) | TBD |
| CANopen variant on a CAN FD bus | TBD. Classic CANopen (CiA 301) uses classic CAN frames. CANopen FD (CiA 1301) uses CAN FD frames and replaces SDO with USDO. The examples on this page use classic CANopen. |
CAN IDs
CANopen derives most CAN IDs from the node ID (1 to 127). These are the defaults of the CiA 301 predefined connection set.
| Object | CAN ID | Sent by |
|---|---|---|
| NMT command | 0x000 | Host |
| SYNC | 0x080 | Host |
| EMCY (emergency) | 0x080 + node ID | Drive |
| TPDO1 to TPDO4 | 0x180, 0x280, 0x380, 0x480 + node ID | Drive |
| RPDO1 to RPDO4 | 0x200, 0x300, 0x400, 0x500 + node ID | Host |
| SDO response | 0x580 + node ID | Drive |
| SDO request | 0x600 + node ID | Host |
| Heartbeat and boot-up | 0x700 + node ID | Drive |
The CAN IDs for UDS are on the UDS diagnostics page.
Network management (NMT)
An NMT command is a two-byte frame on CAN ID 0x000: the command, then the node ID. Node ID 0 addresses every node.
| Command | Byte 0 | Example: all nodes |
|---|---|---|
| Start (go to operational) | 0x01 | cansend can0 000#0100 |
| Stop | 0x02 | cansend can0 000#0200 |
| Enter pre-operational | 0x80 | cansend can0 000#8000 |
| Reset node | 0x81 | cansend can0 000#8100 |
| Reset communication | 0x82 | cansend can0 000#8200 |
To address one node, put its node ID in byte 1. For node 0x0A: cansend can0 000#010A.
SDOs work in pre-operational and operational. PDOs work only in operational.
The heartbeat frame (0x700 + node ID) carries the NMT state in its one data byte:
| Byte | State |
|---|---|
| 0x00 | Boot-up (sent once at start) |
| 0x04 | Stopped |
| 0x05 | Operational |
| 0x7F | Pre-operational |
The heartbeat period is object 0x1017, in ms; 0 switches the heartbeat off. The factory value is TBD.
Read and write objects (SDO)
SDO transfers read (upload) and write (download) one object at a time. Each request gets a response. Use SDOs for set-up, not for control loops.
With python-canopen and the device description file, address objects directly:
node = network.add_node(node_id, "<device-description-file>.eds")
statusword = node.sdo[0x6041].raw
node.sdo[0x6040].raw = 0x0006
Without the file, transfer raw bytes as in Getting started: node.sdo.upload(0x6041, 0) and node.sdo.download(0x6040, 0, data).
Raw SDO frames
You can also send SDO requests with cansend. Read the statusword (0x6041, sub-index 0) from node NN:
cansend can0 6NN#4041600000000000
The drive answers on 0x580 + node ID:
can0 5NN [8] 4B 41 60 00 40 02 00 00
Byte 0 = 0x4B means two data bytes follow the index. Bytes 1–2 are the index (little-endian), byte 3 the sub-index, bytes 4–5 the value: 0x0240 in this example.
Write 0x0006 to the controlword (0x6040):
cansend can0 6NN#2B40600006000000
The drive answers 60 40 60 00 00 00 00 00 when it accepts the write.
| Byte 0 | Meaning |
|---|---|
| 0x40 | Upload request (read) |
| 0x4F, 0x4B, 0x47, 0x43 | Upload response with 1, 2, 3, 4 data bytes |
| 0x2F, 0x2B, 0x27, 0x23 | Download request (write) with 1, 2, 3, 4 data bytes |
| 0x60 | Download response: write accepted |
| 0x80 | Abort. Bytes 4–7 hold the abort code (little-endian). |
Troubleshooting lists common abort codes.
CiA 402 state machine
The drive accepts motion commands only in the state Operation enabled. You move between states by writing the controlword (0x6040) and you read the state from the statusword (0x6041).
power on
│
▼
Not ready to switch on
│ automatic
▼
Switch on disabled ◄────────────── Fault
│ Shutdown 0x0006 ▲ Fault reset 0x0080
▼ │ leads back to Switch on disabled
Ready to switch on │
│ Switch on 0x0007 Fault reaction active
▼ ▲
Switched on │ any fault, from any state
│ Enable operation 0x000F
▼
Operation enabled ── Quick stop 0x0002 ──► Quick stop active
In CiA 402 the drive function, and so torque, is enabled only in Operation enabled and, while a quick stop runs, in Quick stop active. On a fault the drive switches torque off and the joint moves freely. The drive's quick stop behaviour (0x605A) is TBD.
Read the state
Mask the statusword and compare:
| State | Mask | Value |
|---|---|---|
| Not ready to switch on | 0x004F | 0x0000 |
| Switch on disabled | 0x004F | 0x0040 |
| Ready to switch on | 0x006F | 0x0021 |
| Switched on | 0x006F | 0x0023 |
| Operation enabled | 0x006F | 0x0027 |
| Quick stop active | 0x006F | 0x0007 |
| Fault reaction active | 0x004F | 0x000F |
| Fault | 0x004F | 0x0008 |
Statusword bits:
| Bit | Name |
|---|---|
| 0 | Ready to switch on |
| 1 | Switched on |
| 2 | Operation enabled |
| 3 | Fault |
| 4 | Voltage enabled |
| 5 | Quick stop (0 = quick stop active) |
| 6 | Switch on disabled |
| 7 | Warning |
| 8 | Manufacturer-specific: TBD |
| 9 | Remote |
| 10 | Target reached |
| 11 | Internal limit active |
| 12–13 | Mode-specific |
| 14–15 | Manufacturer-specific: TBD |
Change the state
| Command | Controlword | From | To | CiA 402 transition |
|---|---|---|---|---|
| Shutdown | 0x0006 | Switch on disabled, Switched on, Operation enabled | Ready to switch on | 2, 6, 8 |
| Switch on | 0x0007 | Ready to switch on | Switched on | 3 |
| Disable operation | 0x0007 | Operation enabled | Switched on | 5 |
| Enable operation | 0x000F | Switched on | Operation enabled | 4 |
| Disable voltage | 0x0000 | Ready to switch on, Switched on, Operation enabled, Quick stop active | Switch on disabled | 7, 10, 9, 12 |
| Quick stop | 0x0002 | Operation enabled | Quick stop active | 11 |
| Fault reset | 0x0080 (rising edge of bit 7) | Fault | Switch on disabled | 15 |
Controlword bits 0–3 are Switch on, Enable voltage, Quick stop (active low) and Enable operation. Bit 7 is Fault reset, bit 8 is Halt. The drive's response to Halt is TBD.
To clear a fault: remove the cause, write 0x0080, then continue with Shutdown (0x0006), which clears bit 7 again.
Modes of operation
Write the mode to 0x6060. Read 0x6061 to confirm that the drive has switched; the change is not immediate. Bit n of 0x6502 shows whether the drive supports a mode.
| 0x6060 value | Mode | 0x6502 bit |
|---|---|---|
| 1 | Profile position | 0 |
| 3 | Profile velocity | 2 |
| 4 | Profile torque | 3 |
| 6 | Homing | 5 |
| 7 | Interpolated position | 6 |
| 8 | Cyclic synchronous position | 7 |
| 9 | Cyclic synchronous velocity | 8 |
| 10 | Cyclic synchronous torque | 9 |
Which modes the drive supports is TBD.
Standard objects
These are the CiA 301 and CiA 402 objects used on these pages. Which of them the drive implements is TBD.
| Index | Name | Type | Unit or content |
|---|---|---|---|
| 0x1000 | Device type | UNSIGNED32 | Lower 16 bits = 0x0192 (402) |
| 0x1001 | Error register | UNSIGNED8 | 0 = no error |
| 0x1003 | Pre-defined error field | ARRAY of UNSIGNED32 | Error history |
| 0x1010 | Store parameters | UNSIGNED32 | Write 0x65766173 ("save") |
| 0x1011 | Restore default parameters | UNSIGNED32 | Write 0x64616F6C ("load") |
| 0x1017 | Producer heartbeat time | UNSIGNED16 | ms |
| 0x1018 | Identity object | RECORD | :01 vendor ID, :02 product code, :03 revision, :04 serial number |
| 0x1400–0x1403 | RPDO communication parameters | RECORD | COB-ID, transmission type |
| 0x1600–0x1603 | RPDO mapping | RECORD | Mapped objects |
| 0x1800–0x1803 | TPDO communication parameters | RECORD | COB-ID, transmission type, event timer |
| 0x1A00–0x1A03 | TPDO mapping | RECORD | Mapped objects |
| 0x603F | Error code | UNSIGNED16 | Last error |
| 0x6040 | Controlword | UNSIGNED16 | See above |
| 0x6041 | Statusword | UNSIGNED16 | See above |
| 0x605A | Quick stop option code | INTEGER16 | Quick stop behaviour |
| 0x6060 | Modes of operation | INTEGER8 | See above |
| 0x6061 | Modes of operation display | INTEGER8 | Active mode |
| 0x6064 | Position actual value | INTEGER32 | Position units (TBD) |
| 0x606C | Velocity actual value | INTEGER32 | Velocity units (TBD) |
| 0x6071 | Target torque | INTEGER16 | Per mille of rated torque |
| 0x6072 | Max torque | UNSIGNED16 | Per mille of rated torque |
| 0x6076 | Motor rated torque | UNSIGNED32 | mN·m (TBD) |
| 0x6077 | Torque actual value | INTEGER16 | Per mille of rated torque |
| 0x607A | Target position | INTEGER32 | Position units (TBD) |
| 0x60FF | Target velocity | INTEGER32 | Velocity units (TBD) |
| 0x6502 | Supported drive modes | UNSIGNED32 | Bit field, see above |
Drive-specific objects (0x2000–0x5FFF) are not defined yet.
Cyclic control with PDOs and SYNC
A PDO is one CAN frame that carries mapped objects with no request and no response. Use PDOs for control loops. With synchronous PDOs the host sends a SYNC frame (0x080) each cycle; the drive applies the last RPDO and sends its TPDOs at each SYNC.
This example maps:
| PDO | Direction | Contents | Transmission type |
|---|---|---|---|
| RPDO1 | Host → drive | Controlword 0x6040, target torque 0x6071 | 1: applied at the next SYNC |
| TPDO1 | Drive → host | Statusword 0x6041, torque actual value 0x6077 | 1: sent after every SYNC |
| TPDO2 | Drive → host | Position actual value 0x6064, velocity actual value 0x606C | 1: sent after every SYNC |
It then enables the drive in cyclic synchronous torque mode (10) through RPDO1, applies a torque for 0.5 s and prints position, velocity and torque. The SYNC period limits of the drive are TBD.
Warning Keep hands, cables and tools away from the output face while the script runs.
import sys
import time
import canopen
node_id = int(sys.argv[1], 0) # node ID, e.g. 0x0A
eds = sys.argv[2] # path to the device description file (not released yet)
torque = int(sys.argv[3]) # target torque in per mille of rated torque (0x6076)
PERIOD_S = 0.002 # SYNC period; the drive's limits are TBD
network = canopen.Network()
network.connect(interface="socketcan", channel="can0")
node = network.add_node(node_id, eds)
# PDO mapping can only change in NMT pre-operational.
node.nmt.state = "PRE-OPERATIONAL"
node.rpdo.read()
node.rpdo[1].clear()
node.rpdo[1].add_variable(0x6040) # controlword
node.rpdo[1].add_variable(0x6071) # target torque
node.rpdo[1].trans_type = 1 # act on the next SYNC
node.rpdo[1].enabled = True
node.rpdo.save()
node.tpdo.read()
node.tpdo[1].clear()
node.tpdo[1].add_variable(0x6041) # statusword
node.tpdo[1].add_variable(0x6077) # torque actual value
node.tpdo[1].trans_type = 1 # send after every SYNC
node.tpdo[1].enabled = True
node.tpdo[2].clear()
node.tpdo[2].add_variable(0x6064) # position actual value
node.tpdo[2].add_variable(0x606C) # velocity actual value
node.tpdo[2].trans_type = 1
node.tpdo[2].enabled = True
node.tpdo.save()
node.sdo[0x6072].raw = abs(torque) # max torque
node.sdo[0x6060].raw = 10 # cyclic synchronous torque
rpdo = node.rpdo[1]
rpdo[0x6040].raw = 0x0006 # Shutdown
rpdo[0x6071].raw = 0
rpdo.start(PERIOD_S) # send RPDO1 every period
network.sync.start(PERIOD_S) # send SYNC every period
node.nmt.state = "OPERATIONAL"
def wait_for_state(mask, value, timeout_s=1.0):
end = time.monotonic() + timeout_s
while time.monotonic() < end:
node.tpdo[1].wait_for_reception(timeout=0.1)
if node.tpdo[1][0x6041].raw & mask == value:
return
raise RuntimeError(f"statusword 0x{node.tpdo[1][0x6041].raw:04X}")
try:
wait_for_state(0x006F, 0x0021) # Ready to switch on
rpdo[0x6040].raw = 0x0007 # Switch on
wait_for_state(0x006F, 0x0023)
rpdo[0x6040].raw = 0x000F # Enable operation
wait_for_state(0x006F, 0x0027)
rpdo[0x6071].raw = torque
end = time.monotonic() + 0.5
while time.monotonic() < end:
node.tpdo[2].wait_for_reception(timeout=0.1)
print(node.tpdo[2][0x6064].raw, node.tpdo[2][0x606C].raw, node.tpdo[1][0x6077].raw)
finally:
rpdo[0x6071].raw = 0
rpdo[0x6040].raw = 0x0006 # Shutdown: torque off
time.sleep(0.05)
network.sync.stop()
rpdo.stop()
node.nmt.state = "PRE-OPERATIONAL"
network.disconnect()
Run it:
python3 pdo_torque.py <node-id> <device-description-file>.eds <torque>
Note python-canopen sends the RPDO and the SYNC from two separate timers, so they are not locked in phase. That is enough for a test. In a real control loop, send the RPDO and then the SYNC once per cycle from a single loop.
Emergency messages (EMCY)
The drive sends an EMCY frame on 0x080 + node ID when an error occurs, and again when it clears. Watch for them with:
candump can0,080:780
The filter also passes the SYNC frame (0x080) if the host sends SYNC.
| Bytes | Content |
|---|---|
| 0–1 | Error code, little-endian. 0x0000 = error reset or no error. |
| 2 | Error register (copy of 0x1001) |
| 3–7 | Manufacturer-specific: TBD |
The high byte of the error code gives the error class (CiA 301):
| Error code | Class |
|---|---|
| 0x10xx | Generic |
| 0x2xxx | Current |
| 0x3xxx | Voltage |
| 0x4xxx | Temperature |
| 0x5xxx | Device hardware |
| 0x6xxx | Device software |
| 0x7xxx | Additional modules |
| 0x8xxx | Monitoring |
| 0x9xxx | External error |
| 0xF0xx | Additional functions |
| 0xFFxx | Device-specific |
The error codes the drive uses are TBD. The same faults are readable as diagnostic trouble codes over UDS.
In python-canopen, read EMCY messages from node.emcy:
node.emcy.add_callback(lambda e: print(f"EMCY 0x{e.code:04X} register 0x{e.register:02X}"))
ROS 2
A ROS 2 driver is part of the design. It is not released, and its interface is not defined yet.